KH 8384-5 EN
123
Parameter lists
DI FB:
MODE_BLK (5)
Storage class N; read/write capability r/w; supported modes O/M/A
Operating mode
– Target Mode (Code 48 t4 for DI1
Code 48 t7 for DI2)
– Actual Mode (read only)
– Permitted Mode
– Normal Mode (read only)
•
O/S · The DI Function Block is not executed. The last value is issued at the output OUT_D.
•
MAN · The output value of the DI Function Block can be entered manually by the operator
over the OUT_D parameter.
•
AUTO · The binary input value (FIELD_VAL_D) is processed by the function block and
issued as OUT_D.
DI FB:
OUT_D (8)
Storage class S; read/write capability r/w; supported modes O/M
Discrete output variable (value and status)
Code 48 I4/5 for DI1
Code 48 L4/5 for
DI2
DI FB:
PV_D (7)
Storage class D; read capability r
Indicates the discrete state (including status) used for the function block.
Note:
In AUTO mode, the PV_D parameter is identical with output OUT_D.
DI FB:
PV_FTIME (16)
Storage class S; read/write capability r/w; supported modes O/M/A
Filter time constant [s] of the digital filter until a binary state at the input of the function block
is adopted in the PV_D parameter.
• [0]
DI FB:
SIMULATE_D (9)
Storage class S; read/write capability r/w; supported modes O/M/A
Simulation: Input of the discrete input value (FIELD_VAL_D) with status
Note:
The simulation can only be activated if it is enabled at the positioner (Code 48 F3)
and in the function block.