Parameter lists
AO TRD: ST_REV (1)
Storage class S; read capability r
Static revision number
Note:
The revision number is incremented with each change of a static parameter in the
block.
AO TRD: SUB_MOD_INIT (118)
Storage class D; read capability r
Indicates whether the initialization was performed in SUB mode (substitute calibration).
AO TRD: TAG_DESC (2)
Storage class S; read/write capability r/w
User-specific text for unique identification and assignment of the block
• Max. 32 characters, [no text]
AO TRD: THRESHOLD_END_POS_RECORDING (207)
Storage class D; read/write capability r/w
Statistical information > Trend of travel end position
Recording threshold
AO TRD: TRANSDUCER_DIRECTORY (9)
· This parameter is not supported.
AO TRD: TRANSDUCER_STATE (102)
Storage class D; read capability r
State of the Transducer Block
Code 48 t2
11 See operating mode
12
Solenoid valve active · Forced venting active
13 Lower travel limit active
14
Upper travel limit active
15
End position < active · Tight-closing of the valve
16
End position > active · Maximum open position of the valve
17 Fail-safe position active
18 Normal operation
AO TRD: TRANSDUCER_TYPE (10)
Storage class D; read capability r
Indicates the type of transducer. “Standard Advanced Positioner Valve” in this case.