KH 8384-5 EN
53
Parameter lists
AO TRD: FINAL_VALUE_D (49)
Storage class S; read/write capability r/w; supported modes O/M
Discrete set point of upstream DO1 Function Block
AO TRD: FINAL_VALUE_RANGE (15)
Storage class S; read/write capability r/w; supported modes O
Travel/angle range
•
FINAL VALUE RANGE EU_100 · Travel/angle range end
Code 9
•
FINAL VALUE RANGE EU_0 · Travel/angle range start
Code 8
•
FINAL VALUE RANGE UNITS_INDEX · Unit
•
FINAL VALUE RANGE DECIMAL · Decimal point
Note:
FINAL_VALUE is sent to the AO Transducer Block directly from an upstream AO
Function Block.
The FINAL_VALUE_RANGE operating range is compared on entering it with TRANS_PIN_
POS. If the TRANS_PIN_POS parameter is changed, the positioner checks whether the
setting and unit match the current operating range FINAL_VALUE_RANGE. If this is not the
case, the FINAL_VALUE_RANGE operating range is set to 0 to 100 %.
AO TRD: FRICTION (68)
Storage class N; read capability r
Determined friction in percent
AO TRD: FRICTION_LIMITS (265)
Storage class S; read/write capability r/w; supported modes O/M/A
Upper/lower friction limits
•
FRICTION_LIMIT_UP, 0 to 1000 % [200 %]
•
FRICTION_LIMIT_DOWN, 0 to 1000 % [50 %]
AO TRD: FRICTION_UNITS (67)
· This parameter is not supported.
AO TRD: FST_BREAKOUT_TIME (86)
Storage class S; read capability r
Breakaway time determined during the last full stroke test (FST)
AO TRD: FST_BREAKOUT_TIMEOUT (87)
Storage class S; read/write capability r/w; supported modes O/M/A
Cancellation conditions of the full stroke test (FST): maximum breakaway time
• 0.0 to 25000.0 s, [7.5 s]