KH 8384-5 EN
39
Parameter lists
•
INTERNAL_TEMP · Current temperature inside the positioner
•
PST_AUTOSTART_READ · Time until next automatic PST start
Default settings:
[VALVE POS] in SELECT_MAI_OUT_1, SELECT_MAI_OUT_4, SELECT_MAI_OUT_7
[INTERNAL_TEMP] in SELECT_MAI_OUT_2, SELECT_MAI_OUT_5, SELECT_MAI_OUT_8
[NEXT_AUTOSTART_READ] in SELECT_MAI_OUT_3, SELECT_MAI_OUT_6
SELECT_MAO_IN_1 to SELECT_MAO_IN_8 · Signal to be processed over the input IN_1…
IN_8 of the MAO Function Block
•
FLOW SENSOR
•
P1 · Pressure p1
•
P2 · Pressure p2
•
PROC TEMP · Process temperature
Default settings:
[FLOW SENSOR] in SELECT_MAO_IN_1, SELECT_MAO_IN_5
[P1] in SELECT_MAO_IN_2, SELECT_MAO_IN_6
[P2] in SELECT_MAO_IN_3, SELECT_MAO_IN_7
[PROC TEMP] in SELECT_MAO_IN_4, SELECT_MAO_IN_8
RES:
SET_FSTATE (29)
Storage class D; read/write capability r/w; supported modes O/A
Activation of the fault state in the AO Function Block
RES:
SHED_RCAS (26)
Storage class S; read/write capability r/w; supported modes O/A
Monitoring time to check connection between fieldbus host system and PID Function Block in
RCAS mode
When the monitoring time has elapsed, the PID Function Block switches from RCAS to the
mode selected in the SHED_OPT parameter.
•
[640000 · ms]
RES:
SHED_ROUT (27)
Storage class S; read/write capability r/w; supported modes O/A
Monitoring time to check connection between fieldbus host system and PID Function Block in
ROUT mode
When the monitoring time has elapsed, the PID Function Block switches from ROUT to the
mode selected in the SHED_OPT parameter.
•
[640000 · ms]