54
KH 8384-5 EN
Parameter lists
AO TRD: FST_COMPLETION_TIMEOUT (90)
Storage class S; read/write capability r/w; supported modes O/M/A
Cancellation conditions of the full stroke test (FST): maximum test duration (user-defined)
• 0.0 to 25000.0 s, [30.0 s]
AO TRD: FST_DIAGR_E1 (257) to FST_DIAGR_E4 (260)
Storage class D; read capability r
Statistical information > Data logger: Measured set point deviation (e) values
AO TRD: FST_DIAGR_TIME1 (245) to FST_DIAGR_TIME4 (248)
Storage class D; read capability r
Tests > Full stroke test (FST): Measured time (t) values
AO TRD: FST_DIAGR_W1 (253) to FST_DIAGR_W4 (256)
Storage class D; read capability r
Statistical information > Data logger: Measured set point (w) values
AO TRD: FST_DIAGR_X1 (249) to FST_DIAGR_X4 (252)
Storage class D; read capability r
Statistical information > Data logger: Measured valve position (x) values
AO TRD: FST_DIAGR_Y1 (261) to FST_DIAGR_Y4 (264)
Storage class D; read capability r
Statistical information > Data logger: Measured drive signal (y) values
AO TRD: FST_DISPLAY (238)
Storage class D; read capability r
Information on the full stroke test (FST)
•
FST_PROGRESS_FLAG · Current progress of the test
•
FST_STATUS_PST · Status (successful/not successful)
•
FST_NUMBERS_OF_TESTS · Number of full stroke tests performed
•
FST_SETTINGS_MIN_SCAN_RATE · Recommended min. scan rate
•
FST_SETTINGS_DURATION_TEST · Expected duration of test