Parameter lists
AO TRD: LS_TEST_INFORMATION (273)
Storage class D; read capability r
Leakage sensor: test status
AO TRD: MIN_CLEARANCE_NEW_LOGGING_MGV (107)
Storage class S; read/write capability r/w; supported modes O/M/A
Minimum time interval until logging of the internal solenoid valve restarts (error control)
AO TRD: MODE_BLK (5)
Storage class S; read/write capability r/w
Operating mode
– Target Mode
Code 48 t0
– Actual Mode (read only)
Code 48 t1
– Permitted Mode
– Normal Mode (read only)
•
AUTO · A positioning value is calculated from the output value received from the AO
Function Block and the control valve is positioned accordingly.
•
O/S · The positioning value from the AO Function Block is not used. The control valve is
moved to its mechanical fail-safe position entered in ACT_FAIL_ACTION. The mode is
also changed to O/S when the forced venting function is activated.
•
MAN · The positioning value (FINAL_VALUE) can be entered manually (reading at the
positioner: and )
•
LO · AO TRD switches to LO mode if the positioner is switched to the MAN mode on
site.
AO TRD: NO_OF_ZERO_POINT_ADJ (137)
Storage class D; read capability r
Number of zero calibrations performed since the last initialization
Code 48 d3
AO TRD: OPTI_SUB_INIT (119)
Storage class S; read/write capability r/w; supported modes O/M/A
Optimizes edges of substitute calibration
• ON
• [OFF]