62
KH 8384-5 EN
Parameter lists
AO TRD: POS_ALERT_HI (24)
Storage class S; read/write capability r/w; supported modes O/M/A
User-defined high limit which sets the high limit bit in WORKING_ POS when the value is
exceeded.
•
[100 %]
AO TRD: POS_ALERT_LO (25)
Storage class S; read/write capability r/w; supported modes O/M/A
User-defined low limit which sets the low limit bit in WORKING_ POS when the value falls
below the limit.
•
[0 %]
AO TRD: POS_DEADBAND (70)
· This parameter is not supported.
AO TRD: POS_FEATURES (55)
Storage class D; read capability r
Parameter groups supported by AO TRD
AO TRD: PRESSURE_LIMIT (125)
Storage class S; read/write capability r/w
Pressure limit
Code 16
• [OFF]
•
3.7 bar
•
2.4 bar
•
1.4 bar
AO TRD: PROTOKOLL_BSZ_START (141)
Storage class D; read capability r
Display the time since first start-up (operating hours counter)
AO TRD: PST_AUTOSTART_READ (203)
Storage class D; read capability r; supported modes O/M/A
Time until the next automatically performed partial stroke test (Auto PST)
AO TRD: PST_BREAKOUT_TIME (77)
Storage class N; read capability r
Breakaway time determined during the last partial stroke test (PST)