Parameter lists
PID FB:
RESET (24)
Storage class S; read/write capability r/w
Time constant for integral function
• [3402823466 x 10
38
] (maximum possible value)
Note:
The cold start value or '0' switches off the integral function.
PID FB:
ROUT_IN (33)
Storage class N; read/write capability r/w; supported modes ALL
Out value (value and status)
ROUT_IN is provided by the fieldbus host system.
Note:
This parameter is only active in ROUT mode.
PID FB:
ROUT_OUT (36)
Storage class D; read capability r
Analog set point (value and status) read over the ROUT_IN parameter
ROUT_OUT value is provided to the fieldbus host system to perform back-calculations in
case of control mode changes or limited signals.
Note:
This parameter is only active in ROUT mode.
PID FB:
SHED_OPT (34)
Storage class S; read/write capability r/w; supported modes ALL
Behavior upon exceeding the monitoring time (SHED_RCAS parameter in the RES block)
while checking the connection between the fieldbus host system and the PID Function Block
in RCAS or ROUT.
When the monitoring time has elapsed, PID Function Block switches from RCAS or ROUT
to the selected operating mode. The action to be taken after the fault state ends is also
determined.
•
[UNINITIALIZED]
•
NORMAL SHED_NORMAL RETURN · On failure of remote connection, change to next
possible mode until RCAS or ROUT mode is restored.
•
NORMAL SHED_NO RETURN · On failure of remote connection, change to next
possible mode. The block remains in this mode.