56
KH 8384-5 EN
Parameter lists
AO TRD: FST_TEST_INFO (235)
Storage class D; read capability r
Current status of the full stroke test (FST)
AO TRD: FST_TEST_STAT1 (274) to FST_TEST_STAT3 (276)
Storage class D; read capability r
Status of the full stroke test (FST)
FST_TEST_STAT1 (274) = Current test
FST_TEST_STAT2 (275) = First saved status
FST_TEST_STAT3 (276) = Second saved status
•
FST_NO_TEST_AVAILABLE · No test available
•
FST_MAX_TIME_EXCEEDED · Max. test duration exceeded
•
FST_TEST_MANUA_CANCEL · Test canceled manually
•
FST_OUT_OF_MEMORY · Measured data memory full
•
FST_ABO_INT_SOL_VALVE · Canceled due to internal solenoid valve/forced venting
•
FST_PRESSURE_FRICTION · Canceled due to supply air/friction
•
FST_CURRENT_TOO_LOW · Test canceled, insufficient current
AO TRD: HIST (135)
Storage class D; read capability r
Reading in hours (or part thereof)
•
HIS_T_ZEIT_MIN_TEMPERATURE · Operating hours counter: lowest temperature inside
the positioner
•
HIS_T_ZEIT_MAX_TEMPERATURE · Operating hours counter: highest temperature inside
the positioner
•
TEMP_PERIOD_TIME_LOW · Time the temperature remained below –40 °C (–40 °F)
•
TEMP_PERIOD_TIME_HIGH · Time the temperature remained above +80 °C (+176 °F)
AO TRD: HISTOGR_X_SCAN_RATE (150)
Storage class D; read/write capability r/w; supported modes O/M/A
Statistical information > Short-term valve position x histogram: measured values and mean
value
AO TRD: HISTOGR_X_SHORT (149)
Storage class D; read capability r
Statistical information > Short-term valve position x histogram: scan rate to record valve
positions