
104
KH 8384-5 EN
Parameter lists
PID FB:
HI_ALM (61)
Storage class D; read capability r
Alarm for the high pre-alarm limit (HI_LIM) including details on the date and time as well
as the value at which the alarm is triggered.
•
Unit of PV_SCALE
PID FB:
HI_HI_ALM (60)
Storage class D; read/write capability r/w
Alarm for the high-high alarm limit (HI_HI_LIM) including details on the date and time as
well as the value at which the alarm is triggered.
•
Unit of PV_SCALE
Note:
Additionally, the active alarm can be confirmed manually in this parameter group.
PID FB:
HI_HI_LIM (49)
Storage class S; read/write capability r/w; supported modes ALL
High-high alarm limit (HI_HI_ALM)
•
Range and unit of PV_SCALE, [3402823466 x 10
38
]
If PV exceeds this limit, the alarm state parameter HI_HI_ALM is issued.
PID FB:
HI_HI_PRI (48)
Storage class S; read/write capability r/w; supported modes ALL
Behavior upon exceeding the high-high alarm limit HI_HI_LIM
•
[0] · The violation of the high-high alarm limit is not analyzed.
•
1 · No notification upon violation of the high-high alarm limit
•
2 · Reserved for block alarms
•
3 to 7 · The violation of the high-high alarm limit is issued to notify the operator with the
corresponding priority: (3 = low, 7 = high)
•
8 to 15 · The violation of the high-high alarm limit is issued as a critical alarm with the
corresponding priority: (8 = low, 15 = high)
PID FB:
HI_LIM (51)
Storage class S; read/write capability r/w; supported modes ALL
Alarm limit for the high pre-alarm HI_ALM
•
Range and unit of PV_SCALE, [3402823466 x 10
38
]
If PV exceeds this limit, the alarm state parameter HI_ALM is issued.