KH 8384-5 EN
33
Parameter lists
RES:
FD_OFFSPEC_MAP (48)
Storage class S; read/write capability r/w
Classification of diagnostic messages with the 'Out of specification' status
RES:
FD_OFFSPEC_MASK (52)
Storage class S; read/write capability r/w
Activation/deactivation of diagnostic messages with the 'Out of specification' status
RES:
FD_OFFSPEC_PRI (60)
Storage class S; read/write capability r/w
Determines the priority of diagnostic messages with the 'Out of specification' status
RES:
FD_RECOMMEN_ACT (64)
Storage class D; read/write capability r
Recommended action
RES:
FD_SIMULATE (63)
Storage class S; read/write capability r/w
Simulation of diagnostic messages
RES:
FD_VER (42)
Storage class S; read/write capability r
Field diagnostic specification version
• [1]
RES:
FEATURES (17)
Storage class S; read capability r
Additional functions supported by the device, see FEATURES_SEL
RES:
FEATURES_SEL (18)
Storage class S; read/write capability r/w; supported modes O/A
Selects the additional functions supported by the device
•
REPORTS · Fieldbus host system needs to acknowledge receipt of the event report.
•
HARD W LOCK · Write lock switch hardware is assessed.
•
FAULTSTATE · Fault state can be triggered (see SET_FSTATE/CLR_FSTATE).
•
OUT READBACK · Current valve position issued in the PV parameter of the Analog
Function Block (otherwise in SP parameter).
Note:
If the AO Function Block is not to move to the MAN mode when the forced venting
function is activated or the solenoid valve is triggered, deactivate this option.