Parameter lists
AO TRD: TRANSDUCER_TYPE_VER (11)
Storage class D; read capability r
Transducer Block for positioner according to Specification FF-90
AO TRD: TRANSM_PIN_POS (115)
Storage class S; read/write capability r/w
Pin position
Code 4
AO TRD: TRAVEL_ACCUM (29)
Storage class D; read capability r
Total valve travel: totaled double valve travel
Code 23
AO TRD: TRAVEL_ACCUM_DEADBAND (73)
· This parameter is not supported.
AO TRD: TRAVEL_ACCUM_LIM (94)
· This parameter is not supported.
AO TRD: TRAVEL_ACCUM_UNITS (95)
· This parameter is not supported.
AO TRD: TRAVEL_UNITS (30)
Storage class S; read/write capability r/w; supported modes O/M/A
Unit of valve travel according to Table TN-016
•
[%] or [°], in the event that the positioner is not initialized
AO TRD: TRIP_TIMEOUT (74)
· This parameter is not supported.
AO TRD: TV_STEP (128)
Storage class S; read/write capability r/w
Derivative-action time TV (step)
Code 18
Note:
This parameter can only be read over FOUNDATION fieldbus. The value is recorded
during initialization.
AO TRD: UPDATE_EVT (7)
Storage class D; read/write capability r/w
Indicates whether static data have been changed, including date and time stamp.
AO TRD: VALVE_MAN_ID (42)
Storage class S; read/write capability r/w; supported modes O/M/A
Manufacturer of the valve on which the positioner is mounted.