Parameter lists
AO TRD: INIT_WITH_REF_TEST (117)
Storage class S; read/write capability r/w
Record diagnostic reference tests during initialization.
• Yes
• [No]
AO TRD: INTERNAL_TEMP (96)
Storage class D; read capability r
Current temperature inside the positioner
AO TRD: INTERNAL_TEMP_MAX (98)
Storage class D; read capability r
Highest temperature measured inside the positioner
AO TRD: INTERNAL_TEMP_MIN (97)
Storage class D; read capability r
Lowest temperature measured inside the positioner
AO TRD: INTERNAL_TEMP_UNITS (99)
Storage class S; read/write capability r/w; supported modes O/M/A
Unit of temperature inside the positioner: [°C], °F
AO TRD: KP_STEP (127)
Storage class S; read/write capability r/w
Proportional-action coefficient Kp level
Code 17
Note:
This parameter can only be read over FOUNDATION fieldbus. The value is recorded
during initialization.
AO TRD: LIMIT_VALUE_TIME_ANALYSIS (145)
Storage class S; read/write capability r/w; supported modes O/M/A
Statistical information > Open/close: time limit for difference between reference value and
currently recorded value
Determines at which value a message is generated.
• 0.0 to 30.0 s, [0.6 s]
AO TRD: LIMIT_VALUE_TRAVEL_ANALYSIS (146)
Storage class S; read/write capability r/w; supported modes O/M/A
Statistical information > Open/close: travel limit for difference between reference value
and currently recorded value
Determines at which value a message is generated.
•
0.0 … 100.0 %, [0.3 %]