Code
no.
Parameter
– Readings,
values [default setting]
Description
Note:
Codes with marked with an asterisk (*) must be enabled with
Code 3
prior to configuration.
d5* Zero point limit
0.0 to 100.0 % of the nom-
inal range · ESC, [5.0]
Valve position limit in relation to the nominal range
When the limit is exceeded, a 'Zero point' message (
Code 58
) is
generated according to the status classification selected.
Note:
The 'Zero point' message (Code 58) has the default status
classification 'Maintenance required'. This classification can only
be changed in the operator software (e.g. TROVIS-VIEW 4) .
d6 Condensed state
Read only
Summary of all the classified status messages according to the
NAMUR Recommendation NE 107
OK:
No message
C:
Maintenance required
CR:
Maintenance demanded
S:
Out of specification
B:
Failure
I:
Function check
d7 Supply pressure p
s
Read only
Current supply pressure [bar]
d8 Signal pressure p
out
Read only
Current signal pressure [bar]
d9 Flow rate
Read only
Current flow rate through the valve
Note:
– – – – appears on the display when the flow rate calcula-
tion is not active or has failed.
d10 Differential pressure
Read only
Current differential pressure [bar]
d11* Direction of action (actuator)
[-/-] · SA · DA · ELSE · ESC
Indicates the actuator's direction of action
SA:
Single-acting
DA:
Double-acting
ELSE:
Other
EB 8384-6 EN
95
Code list
Summary of Contents for 3730-6
Page 19: ...EB 8384 6 EN 19...
Page 51: ...EB 8384 6 EN 51...
Page 113: ...EB 8384 6 EN 113...
Page 114: ...114 EB 8384 6 EN...
Page 115: ...EB 8384 6 EN 115...
Page 116: ...116 EB 8384 6 EN...
Page 117: ...EB 8384 6 EN 117...
Page 118: ...118 EB 8384 6 EN...
Page 119: ...EB 8384 6 EN 119...
Page 120: ...120 EB 8384 6 EN...
Page 123: ...EB 8384 6 EN 123 diagnostic functions 11 Z Zero calibration 68 Index...