Code
no.
Parameter
– Readings,
values [default setting]
Description
Note:
Codes with marked with an asterisk (*) must be enabled with
Code 3
prior to configuration.
37 Options
Read only
Indicates which option (connected to terminals 31 and 32,
Fig. 18) is installed:
No:
No option installed
POS:
Analog position transmitter
dI:
Binary input
LS:
Leakage sensor
When the binary input is used,
DI
and
HIGH
or
LOW
status are
displayed in alternating sequence.
When the leakage sensor is used,
LS
and the detected sound
level in dB are displayed in alternating sequence.
38* Inductive limit switch
[No] · YES · ESC
Indicates whether the inductive contact option is installed.
39 Set point deviation e
Read only
Shows the set point deviation (e = w – x)
40 Min. transit time OPEN
Read only
Minimum opening time determined during initialization
41 Min. transit time CLOSED
Read only
Minimum closing time determined during initialization
42 Set point
Read only
Set point w applied for automatic mode
4 to 20 mA corresponds with 0 to 100 %
43 Firmware version
Read only
Device type and current firmware version (displayed in alter-
nating sequence)
44 Info y
Read only
Control signal y in %, in relation to the travel range determined
during initialization
MAX: The positioner builds up its maximum output pressure.
See description for
Code 14, 15
.
0 P:
The positioner vents completely. See description for
Code
14, 15
.
– – –: The positioner is not initialized.
EB 8384-6 EN
93
Code list
Summary of Contents for 3730-6
Page 19: ...EB 8384 6 EN 19...
Page 51: ...EB 8384 6 EN 51...
Page 113: ...EB 8384 6 EN 113...
Page 114: ...114 EB 8384 6 EN...
Page 115: ...EB 8384 6 EN 115...
Page 116: ...116 EB 8384 6 EN...
Page 117: ...EB 8384 6 EN 117...
Page 118: ...118 EB 8384 6 EN...
Page 119: ...EB 8384 6 EN 119...
Page 120: ...120 EB 8384 6 EN...
Page 123: ...EB 8384 6 EN 123 diagnostic functions 11 Z Zero calibration 68 Index...