For other actuator sizes or travels, select the
lever and pin position from the travel table
on page 21. Lever
L
and
XL
are included in
the mounting kit.
3. Place the lever (1) and disk spring (1.2)
on the sensor shaft.
Place the lever (1)
in mid-position
and
hold it in place
. Screw on the nut (1.1).
4. Screw both bolts (14) to the bracket
(9.1) of the stem connector (9). Attach
the follower plate (3) and fix with the
screws (14.1).
5. Place the bracket with the sensor at the
NAMUR rib in such a manner that the
follower pin (2) rests in the slot of the
follower plate (3), then screw the
bracket using its fixing screws onto the
valve.
4.6.3 Mounting the position sen-
sor to Type 3510 Mi-
cro-flow Valve
For the required mounting parts and acces-
sories, refer to Table 7 on page 44.
1. Place the lever (1)
in mid-position
and
hold it in place
. Unscrew the nut (1.1)
and remove the standard attached lever
M
(1) together with the disk spring
(1.2) from the sensor shaft.
2. Screw the position sensor (20) onto the
bracket (21).
3. Select the lever
S
(1) from the accesso-
ries and screw the follower pin (2) into
the hole for pin position
17
.
Place the lever (1) and disk spring (1.2)
on the sensor shaft.
EB 8384-6 EN
37
Attachment to the control valve – Mounting parts and accessories
20
21
1.1
1.2
1
3
2
Fig. 15 · Mounting on a micro-flow valve
1
Lever
1.1 Nut
1.2 Disk spring
2
Follower pin
3
Follower clamp
20 Position sensor
21 Bracket
Summary of Contents for 3730-6
Page 19: ...EB 8384 6 EN 19...
Page 51: ...EB 8384 6 EN 51...
Page 113: ...EB 8384 6 EN 113...
Page 114: ...114 EB 8384 6 EN...
Page 115: ...EB 8384 6 EN 115...
Page 116: ...116 EB 8384 6 EN...
Page 117: ...EB 8384 6 EN 117...
Page 118: ...118 EB 8384 6 EN...
Page 119: ...EB 8384 6 EN 119...
Page 120: ...120 EB 8384 6 EN...
Page 123: ...EB 8384 6 EN 123 diagnostic functions 11 Z Zero calibration 68 Index...