5.2.2 Establishing communication
Communication between PC and positioner
(via FSK modem or handheld communicator,
if necessary, using an isolation amplifier) is
based on the HART
®
protocol.
Type Viator FSK modem
RS 232
not ex.
Order no. 8812-0130
PCMCIA
not ex
Order no. 8812-0131
USB
not ex
Order no. 8812-0132
If the supply voltage of the controller or con-
trol station becomes too low because it has
been reduced by the load in the circuit, an
isolation amplifier is to be connected be-
tween controller and positioner (interfacing
as for positioner connected in hazardous ar-
eas, see Fig. 19).
If the positioner is used in hazardous areas,
an explosion-protected isolating amplifier is
to be used.
By means of the HART
®
protocol, all control
room and field devices connected in the
loop are individually accessible through
their address via point-to-point or standard
bus (multidrop).
Point-to-point:
The bus address/polling address must al-
ways be set to zero (0).
Standard bus (multidrop):
In the standard bus (multidrop) mode, the
positioner follows the analog current signal
(reference variable) as for point-to-point
communication. This operating mode is, for
example, suitable for split-range operation
of positioners (series connection). The bus
EB 8384-6 EN
49
Connections
3730-6
3730-6
Fig. 19 · Connection with FSK modem
Explosion-protected isolating amplifier
Connection in safe area
Handheld communicator
or second FSK modem
Handheld communicator
or second FSK modem (explosion-protected)
4 to 20 mA
Safe area
Hazardous area
Controller/control station
Controller/control station
Connection in hazardous area
Summary of Contents for 3730-6
Page 19: ...EB 8384 6 EN 19...
Page 51: ...EB 8384 6 EN 51...
Page 113: ...EB 8384 6 EN 113...
Page 114: ...114 EB 8384 6 EN...
Page 115: ...EB 8384 6 EN 115...
Page 116: ...116 EB 8384 6 EN...
Page 117: ...EB 8384 6 EN 117...
Page 118: ...118 EB 8384 6 EN...
Page 119: ...EB 8384 6 EN 119...
Page 120: ...120 EB 8384 6 EN...
Page 123: ...EB 8384 6 EN 123 diagnostic functions 11 Z Zero calibration 68 Index...