Setting the switching point
:
NOTICE
During adjustment or testing, the switching
point must always be approached from
mid-position (50 %).
To ensure safe switching under any ambient
conditions, the switching point should be ad-
justed to a value of approx. 5 % before the
mechanical stop (OPEN – CLOSED).
For CLOSED position:
1. Initialize positioner.
2. Use the
MAN
function to move the
positioner to 5 % (see LC display).
3. Adjust the tag using the yellow adjust-
ment screw (2) until the tag enters or
leaves the field and the switching am-
plifier responds. You can measure the
switching voltage as an indicator.
Contact function:
4
Tag leaving the field > contact is made
4
Tag entering the field > contact is
opened.
For OPEN position:
1. Initialize positioner.
2. Use the
MAN
function to move the
positioner to 95 % (see LC display).
3. Adjust the tag (1) using the yellow ad-
justment screw (2) until the tag enters or
leaves the field of the proximity switch
(3).
You can measure the switching voltage
as an indicator.
Contact function:
4
Tag leaving the field > Contact is made.
4
Tag entering the field > Contact is
opened.
EB 8384-6 EN
79
Adjusting the limit switch
Summary of Contents for 3730-6
Page 19: ...EB 8384 6 EN 19...
Page 51: ...EB 8384 6 EN 51...
Page 113: ...EB 8384 6 EN 113...
Page 114: ...114 EB 8384 6 EN...
Page 115: ...EB 8384 6 EN 115...
Page 116: ...116 EB 8384 6 EN...
Page 117: ...EB 8384 6 EN 117...
Page 118: ...118 EB 8384 6 EN...
Page 119: ...EB 8384 6 EN 119...
Page 120: ...120 EB 8384 6 EN...
Page 123: ...EB 8384 6 EN 123 diagnostic functions 11 Z Zero calibration 68 Index...