3.7
Technical data
EB 8384-6 EN
15
Design and principle of operation
Type 3730-6 Positioner (technical data in test certificates additionally apply for explosion-protected devices)
Travel, adjustable
Direct attachment to Type 3277:
3.6 to 30 mm
Attachment acc. to IEC 60534-6:
3.6 to 200 mm
Rotary actuators:
24° to 100°
Travel range
Adjustable within the initialized travel/angle of rotation
Travel can be restricted to
1
5
at the maximum
Ref. vari-
able w
Signal range
4 to 20 mA · Two-wire unit with reverse polarity protection · Min. span 4 mA
Static destruc-
tion limit
30 V
Minimum current
3.6 mA for display · Emergency venting at
£
3.8 mA
Load impedance
£
9.2 V (corresponding to 460
W
at 20 mA)
Supply air Supply pres-
sure
1.4 to 7 bar (20 to 105 psi)
Air quality
ISO 8573-1
(2001-02)
Max. particle size and density: Class 4 · Oil content: Class 3
pressure dew point: Class 3 or at least 10 K beneath the lowest ambient temperature to
be expected
Signal pressure (output)
0 bar up to the capacity of supply pressure · Limitable between 1.4 and 7.0 bar by soft-
ware
Character-
istic
Adjustable
Linear, equal percentage, reverse equal percentage, user-defined (by software)
Butterfly, rotary plug and segmented ball valves: linear/equal percentage
Deviation
£
1 %
Hysteresis
£
0.3 %
Sensitivity
£
0.1 %
Transit time
Separately adjustable up to 240 seconds for supply air and exhaust air by software
Direction of action
Reversible
Air consumption, steady
state
Independent from supply pressure approx. 110 l
n
/h
Air output
capacity
Actuator pres-
surized
At
D
p = 6 bar: 8.5 m
n
³/h · At
D
p = 1.4 bar: 3.0 m
n
³/h · K
Vmax (20 °C)
= 0.09
Actuator
vented
At
D
p = 6 bar: 14.0 m
n
³/h · At
D
p = 1.4 bar: 4.5 m
n
³
/h · K
Vmax (20 °C)
= 0.15
Permissible ambient
temperature
–20 to +80 °C for all versions
–45 to +80 °C with metal cable gland
–25 to +80 °C with inductive limit switch (SJ2-S1N) and metal cable gland
Limits in test certificate additionally apply for explosion-protected devices
Influences Temperature
£
0.15 %/10 K
Supply air
None
Vibration
£
0.25 % up to 2000 Hz and 4 g acc. to IEC 770
Electromagnetic
compatibility
Complying with requirements of EN 61000-6-2, EN 61000-6-3, EN 61326-1 and
NAMUR Recommendation NE 21
Summary of Contents for 3730-6
Page 19: ...EB 8384 6 EN 19...
Page 51: ...EB 8384 6 EN 51...
Page 113: ...EB 8384 6 EN 113...
Page 114: ...114 EB 8384 6 EN...
Page 115: ...EB 8384 6 EN 115...
Page 116: ...116 EB 8384 6 EN...
Page 117: ...EB 8384 6 EN 117...
Page 118: ...118 EB 8384 6 EN...
Page 119: ...EB 8384 6 EN 119...
Page 120: ...120 EB 8384 6 EN...
Page 123: ...EB 8384 6 EN 123 diagnostic functions 11 Z Zero calibration 68 Index...