4.3
Attachment to Type 3510
Micro-flow Valve with
Type 3271-5 Actuator
Refer to Table 4 on page 42 for the required
mounting parts and accessories.
Note the travel table on page 21!
The positioner is attached to the valve yoke
using a bracket.
1. Place clamp (3) on the valve stem con-
nector, align at a right angle and screw
tight.
2. Screw bracket (10) to the valve yoke
using two screws (11).
3. Mount connecting plate (6) or pressure
gauge bracket (7) with pressure gauges
to the positioner, making sure both seal
rings (6.1) are seated properly.
NOTICE
The lever must be held stationary in the mid
position while undoing or fastening the nut
to ensure that the lever does not move to one
of the end stops.
4. Unscrew the standard installed lever
M
(1) including follower pin (2) from the
positioner shaft.
5. Take lever
S
(1) and screw follower pin
(2) in the bore for pin position
17
.
6. Place lever S on the positioner shaft
and screw tight using the disk spring
(1.2) and nut (1.1).
7. Place positioner on the bracket (10) in
such a manner that the follower pin
slides into the groove of the clamp (3).
Adjust the lever (1) correspondingly.
Screw the positioner to the bracket (10)
using both screws.
28
EB 8384-6 EN
Attachment to the control valve – Mounting parts and accessories
Summary of Contents for 3730-6
Page 19: ...EB 8384 6 EN 19...
Page 51: ...EB 8384 6 EN 51...
Page 113: ...EB 8384 6 EN 113...
Page 114: ...114 EB 8384 6 EN...
Page 115: ...EB 8384 6 EN 115...
Page 116: ...116 EB 8384 6 EN...
Page 117: ...EB 8384 6 EN 117...
Page 118: ...118 EB 8384 6 EN...
Page 119: ...EB 8384 6 EN 119...
Page 120: ...120 EB 8384 6 EN...
Page 123: ...EB 8384 6 EN 123 diagnostic functions 11 Z Zero calibration 68 Index...