Code
no.
Parameter
– Readings,
values [default setting]
Description
Note:
Codes with marked with an asterisk (*) must be enabled with
Code 3
prior to configuration.
A2* Test
AUTO · [MAN] · ESC
NOTICE
The write protection is active
in the AUTO setting (local
operation and operation
over software locked)
Activates (AUTO) or deactivates (MAN) the time-controlled par-
tial stroke test.
A3* Test interval
Test interval (time and unit of time displayed in alternating se-
quence) until starting the time-controlled test
A4 – Unassigned –
A5 Recommended min. sam-
pling time
Read only
Sampling time [s] used to record entire step response in the
graph of the partial stroke test.
A6 – Unassigned –
A7
D
p_out reference value
Read only
The valve moves to the lower range value (
Code 49 - d2
) and
upper range value (
Code 49 - d3
) with a certain signal pressure.
The
D
p_out reference value [bar]
is calculated from the two
signal pressures.
Note:
The reference value only applies to the adjusted step and
ramp values.
A8* Activate
D
p_out monitoring
[No] · YES · ESC
Activates (YES) or deactivates (No) the
D
p_out monitoring.
A9*
D
p_out monitoring value
0.00 to 7.00 bar · ESC,
[1.00]
The test is canceled whenever the signal pressure change falls
below and exceeds the reference value. The reference value is
made up of
D
p out reference value
(
Code 49 - A7
) and the
D
p_out monitoring value
.
d0 – Unassigned –
d1 – Unassigned –
d2* Lower range value
0.0 to [100.0] % · ESC
Start value of the test
Note:
To perform the partial stroke test, the
Lower range value
must be within the range of the current operating point ±
Toler-
ance limit
.
The
Tolerance limit
is 2.0 % by default. It can be changed in the
operator software, e.g. TROVIS-VIEW 4.
EB 8384-6 EN
97
Code list
Summary of Contents for 3730-6
Page 19: ...EB 8384 6 EN 19...
Page 51: ...EB 8384 6 EN 51...
Page 113: ...EB 8384 6 EN 113...
Page 114: ...114 EB 8384 6 EN...
Page 115: ...EB 8384 6 EN 115...
Page 116: ...116 EB 8384 6 EN...
Page 117: ...EB 8384 6 EN 117...
Page 118: ...118 EB 8384 6 EN...
Page 119: ...EB 8384 6 EN 119...
Page 120: ...120 EB 8384 6 EN...