Enable configuration:
Note:
If no settings are entered within
120 seconds, the enabled configuration
function becomes invalid.
Default
No
Turn
®
Code
3
, display:
No
Press
, Code 3 blinks
Turn
®
YES
Press
, display
Enter pin position and nominal range:
Pin position
Default
No
Nominal range
(locked with Code
4
= No)
Turn
®
Code 4
Press
, Code 4 blinks
Turn
®
Pin position on lever (read rele-
vant section on attachment)
Press
Turn
®
Code 5
Press
, Code 5 blinks
Turn
®
Nominal travel/angle
Press
Select the initialization mode:
Initialization mode
Default
MAX
Turn
®
Code 6
Press
, Code 6 blinks
Turn
®
NOM
Press
to confirm the
NOM
as the initial-
ization mode.
Start initialization:
4
Press INIT key to start initialization!
Note:
If the nominal range determined dur-
ing initialization is smaller than the range
entered in
Code 5
, initialization is canceled
and an error message
(Code 52)
is gener-
ated.
After initialization, check the direction of
action and, if necessary, change it (Code
7).
7.6.3 MAN – Initialization based
on a manually selected
OPEN position
Before starting initialization, move the con-
trol valve manually to the OPEN position.
The positioner calculates the differential
travel/angle from the OPEN and CLOSED
62
EB 8384-6 EN
Start-up – Settings
mm
mm
Summary of Contents for 3730-6
Page 19: ...EB 8384 6 EN 19...
Page 51: ...EB 8384 6 EN 51...
Page 113: ...EB 8384 6 EN 113...
Page 114: ...114 EB 8384 6 EN...
Page 115: ...EB 8384 6 EN 115...
Page 116: ...116 EB 8384 6 EN...
Page 117: ...EB 8384 6 EN 117...
Page 118: ...118 EB 8384 6 EN...
Page 119: ...EB 8384 6 EN 119...
Page 120: ...120 EB 8384 6 EN...
Page 123: ...EB 8384 6 EN 123 diagnostic functions 11 Z Zero calibration 68 Index...