adopts this travel/angle of rotation as the
operating range from 0 to 100 %.
Enable configuration:
Note:
If no settings are entered within
120 seconds, the enabled configuration
function becomes invalid.
Default
No
Turn
®
Code 3
, display:
No
Press
, Code 3 blinks
Turn
®
YES
Press
, display
Enter the pin position:
Pin position
Default
No
Turn
®
Code 4
Press
, Code 4 blinks
Turn
®
Pin position on lever (see relevant
section on attachment)
Press
Turn
®
Skip nominal range (Code 5) and
go to Code 6.
Select the initialization mode:
Default
MAX
Turn
®
Code 6
Press
Turn
®
MAX
Press
to confirm
MAX
as the initialization
mode.
Start initialization:
4
Press INIT key to start initialization!
After initialization, the maximum travel/an-
gle of rotation (
Code 5)
which was detected
during initialization is indicated.
7.6.2 NOM – Initialization based
on nominal range
The calibrated sensor allows the effective
valve travel to be set very accurately. During
the initialization process, the positioner
checks whether the control valve can move
through the indicated nominal range (travel
or angle) without collision. If this is the case,
the indicated nominal range is adopted with
the limits of lower travel/angle range value
(
Code 8
) and upper travel/angle range
value (
Code 9
) as the operating range.
EB 8384-6 EN
61
Start-up – Settings
mm
Summary of Contents for 3730-6
Page 19: ...EB 8384 6 EN 19...
Page 51: ...EB 8384 6 EN 51...
Page 113: ...EB 8384 6 EN 113...
Page 114: ...114 EB 8384 6 EN...
Page 115: ...EB 8384 6 EN 115...
Page 116: ...116 EB 8384 6 EN...
Page 117: ...EB 8384 6 EN 117...
Page 118: ...118 EB 8384 6 EN...
Page 119: ...EB 8384 6 EN 119...
Page 120: ...120 EB 8384 6 EN...
Page 123: ...EB 8384 6 EN 123 diagnostic functions 11 Z Zero calibration 68 Index...