Code
no.
Parameter
– Readings,
values [default setting]
Description
Note:
Codes with marked with an asterisk (*) must be enabled with
Code 3
prior to configuration.
21* Transit time OPEN
(w ramp OPEN)
[0] to 240 s · ESC
NOTICE
The transit time entered in
this code does not apply
when the safety function is
triggered, the solenoid
valve/forced venting is acti-
vated or when the auxiliary
power fails.
The time required to pass through the operating range when the
valve opens.
This parameter can be used to increase the
Min. transit time
OPEN
(
Code 40
).
Limitation of the transit time (
Code 21
and
22
): For some appli-
cations it is advisable to limit the transit time of the actuator to
prevent it from engaging too fast in the running process.
Code 21
has priority over
Code 15
.
22* Transit time CLOSED
(w ramp CLOSED)
[0] to 240 s · ESC
NOTICE
The transit time entered in
this code does not apply
when the safety function is
triggered, the solenoid
valve/forced venting is acti-
vated or when the auxiliary
power fails.
The time required to pass through the operating range when the
valve closes.
This parameter can be used to increase the
Min. transit time
CLOSED
(
Code 41
).
Code 22
has priority over
Code 14
.
23* Absolute total valve travel
YES · [0] to 99 · 10
7
· ESC
Exponential reading after value
reaches 9999
Totaled double valve travel
Can be reset to 0 in Code
36 – STD
and
– DS
.
Note:
The value is saved in a non-volatile memory every 24
hours.
24* Total valve travel limit
1000 to 99 · 10
7
· ESC,
[1 000 000]
Exponential reading after value
reaches 9999
Limit of total valve travel.
A 'Total valve travel exceeded' message is issued with the se-
lected status classification when the limit is exceeded.
Note:
The 'Total valve travel exceeded' message has the default
status classification 'Maintenance required'. This classification
can only be changed in the operator software (e.g. TROVIS-
VIEW 4).
EB 8384-6 EN
89
Code list
Summary of Contents for 3730-6
Page 19: ...EB 8384 6 EN 19...
Page 51: ...EB 8384 6 EN 51...
Page 113: ...EB 8384 6 EN 113...
Page 114: ...114 EB 8384 6 EN...
Page 115: ...EB 8384 6 EN 115...
Page 116: ...116 EB 8384 6 EN...
Page 117: ...EB 8384 6 EN 117...
Page 118: ...118 EB 8384 6 EN...
Page 119: ...EB 8384 6 EN 119...
Page 120: ...120 EB 8384 6 EN...
Page 123: ...EB 8384 6 EN 123 diagnostic functions 11 Z Zero calibration 68 Index...