Triggering the partial stroke test (PST)
A partial stroke test is started when the ref-
erence (w
) moves from the
Operat-
ing point
into the range between 25 and
50 % travel and remains there for longer
than six seconds. The valve (
) moves
from the last defined position to the
Lower
range value (of step)
(
Code 49 - d2
).
After the partial stroke test is completed, the
valve moves back to its previous position
(fail-safe position or
Operating point
).
Canceling the partial stroke test (PST)
The partial stroke test is canceled whenever
the reference variable changes and falls be-
low the
Fail-safe action limit.
The valve
moves back to fail-safe position.
Enable configuration:
Turn
®
Code 3
, display:
No
Press
, Code 3 blinks
Turn
®
YES
Press
, display
Select on/off valve as type of application:
Turn
®
Code 49
Press
, Code 49 blinks
Turn
®
Code h0
Press
, Code h0 blinks
Turn
®
YES
Press
Enter operating point, test limits and limits
for discrete analysis:
Turn
®
Code h1/h2/h3/h4/h5
Press
, Code h1/h2/h3/h4/h5 blinks
Turn
to adjust the parameter selected
Press
to confirm the setting.
70
EB 8384-6 EN
Start-up – Settings
20
40
60
80
100
Start PST
End PST
Time [s]
Travel [%]
t > 6 s
t > 6 s
20
40
60
80
100
Start PST
End PST
Time [s]
Travel [%]
Code 49 - h1
Code 49 - h1 =
Code 49 - d2
Code 49 - h5
Code 49 - h4
Code 49 - h3
Code 49 - h2
Code 49 - d2
Code 49 - h5
Code 49 - h4
Code 49 - h3
Code 49 - h2
Summary of Contents for 3730-6
Page 19: ...EB 8384 6 EN 19...
Page 51: ...EB 8384 6 EN 51...
Page 113: ...EB 8384 6 EN 113...
Page 114: ...114 EB 8384 6 EN...
Page 115: ...EB 8384 6 EN 115...
Page 116: ...116 EB 8384 6 EN...
Page 117: ...EB 8384 6 EN 117...
Page 118: ...118 EB 8384 6 EN...
Page 119: ...EB 8384 6 EN 119...
Page 120: ...120 EB 8384 6 EN...
Page 123: ...EB 8384 6 EN 123 diagnostic functions 11 Z Zero calibration 68 Index...