After initialization, the maximum travel is in-
dicated in mm or the maximum angle in ° in
Code 5
.
7.6.4 MAN2 – Initialization based
on manually selected end
positions
Before starting initialization, move the con-
trol valve manually to the end positions. The
positioner calculates the travel/angle differ-
ence from the positions that the valve moved
to and adopts it as the operating range with
limits of lower travel/angle range value
(
Code 8
) and upper travel/angle range
value (
Code 9
).
Note:
This initialization mode can only be
started when the valve position differs in the
end positions and the positioner has not yet
been initialized.
Enable configuration:
Note:
If no settings are entered within
120 seconds, the enabled configuration
function becomes invalid.
Enable configuration
Default
No
Turn
®
Code
3
, display:
No
Press
, Code 3 blinks
Turn
®
YES
Press
, display
Enter the pin position:
Pin position
Default
No
Turn
®
Code 4
Press
, Code 4 blinks
Turn
®
Pin position on lever (see relevant
section on attachment
Press
Turn
®
Skip nominal range (Code 5) and
go to
Code 6
.
Select the initialization mode and enter end
positions:
Initialization mode
Default
MAX
POS1 (end position 1)
POS2 (end position 2)
Turn
®
Code 6
Press
, Code 6 blinks
64
EB 8384-6 EN
Start-up – Settings
mm
Summary of Contents for 3730-6
Page 19: ...EB 8384 6 EN 19...
Page 51: ...EB 8384 6 EN 51...
Page 113: ...EB 8384 6 EN 113...
Page 114: ...114 EB 8384 6 EN...
Page 115: ...EB 8384 6 EN 115...
Page 116: ...116 EB 8384 6 EN...
Page 117: ...EB 8384 6 EN 117...
Page 118: ...118 EB 8384 6 EN...
Page 119: ...EB 8384 6 EN 119...
Page 120: ...120 EB 8384 6 EN...
Page 123: ...EB 8384 6 EN 123 diagnostic functions 11 Z Zero calibration 68 Index...