8.2
Operating modes
8.2.1 Automatic and manual mo-
des
After initialization has been completed suc-
cessfully, the positioner is in the automatic
mode
(AUTO).
Automatic mode
Switch to manual operating mode
Turn
®
Code
0
Press
, display:
AUTO
, Code
0
blinks
Turn
®
MAN
Press
to change to the manual operating
mode .
The switchover is smooth since the manual
mode starts up with the set point last used
during automatic mode. The current position
is displayed in %.
Adjust the manual set point
Turn
®
Code
1
Press
, Code
1
blinks
Turn
until sufficient pressure has been
built up in the positioner and the control
valve moves to the required position.
Note:
The positioner automatically returns to
Code 0
if no settings are made within 120
seconds. The positioner remains in the man-
ual mode.
Switch to automatic operating mode
(AUTO)
Turn
®
Code
0
Press
, Code
0
blinks
Turn
®
AUTO
Press
. The positioner changes to auto-
matic operating mode.
EB 8384-6 EN
75
Operation
%
%
%
Summary of Contents for 3730-6
Page 19: ...EB 8384 6 EN 19...
Page 51: ...EB 8384 6 EN 51...
Page 113: ...EB 8384 6 EN 113...
Page 114: ...114 EB 8384 6 EN...
Page 115: ...EB 8384 6 EN 115...
Page 116: ...116 EB 8384 6 EN...
Page 117: ...EB 8384 6 EN 117...
Page 118: ...118 EB 8384 6 EN...
Page 119: ...EB 8384 6 EN 119...
Page 120: ...120 EB 8384 6 EN...
Page 123: ...EB 8384 6 EN 123 diagnostic functions 11 Z Zero calibration 68 Index...