Code
no.
Parameter
– Readings,
values [default setting]
Description
Note:
Codes with marked with an asterisk (*) must be enabled with
Code 3
prior to configuration.
33* Error message in case of
'Maintenance required' and
'Out of specification' con-
densed states
[YES] · No · ESC
YES:
'Failure', 'Maintenance required' and 'Out of specifica-
tion' condensed state cause an error message to be gen-
erated.
No:
Only 'Failure' condensed state causes an error message
to be generated.
34* Closing direction
CL · [CCL] · ESC
CL :
Clockwise
CCL:
Counterclockwise
Turning direction in which the valve is moved to the CLOSED po-
sition (view onto the rotary switch motion when the positioner
cover is open).
Note:
Only needs to be entered when the SUB initialization mode
(
Code 6
) is selected.
35* Blocking position
[0] mm/° /% · ESC
Distance up to CLOSED position
Note: Only needs to be entered when the SUB initialization mode
(
Code 6
) is selected.
36* Reset
STD · DIAG · DS · ESC
STD:
Reset start-up
– Parameters are reset to their default settings
– Diagnosis data are reset
– Information parameters (read only) remain unchanged
– Positioner must be re-initialized
DIAG: Reset diagnosis data
– Parameter settings, reference data and logging re-
main unchanged
– Re-initialization not required
DS:
Reset positioner to default settings
– Parameters are reset to their default settings
– Diagnosis data are reset
– Information parameters (read only) are deleted
– Positioner must be re-initialized
92
EB 8384-6 EN
Code list
Summary of Contents for 3730-6
Page 19: ...EB 8384 6 EN 19...
Page 51: ...EB 8384 6 EN 51...
Page 113: ...EB 8384 6 EN 113...
Page 114: ...114 EB 8384 6 EN...
Page 115: ...EB 8384 6 EN 115...
Page 116: ...116 EB 8384 6 EN...
Page 117: ...EB 8384 6 EN 117...
Page 118: ...118 EB 8384 6 EN...
Page 119: ...EB 8384 6 EN 119...
Page 120: ...120 EB 8384 6 EN...
Page 123: ...EB 8384 6 EN 123 diagnostic functions 11 Z Zero calibration 68 Index...