Enter the pin position and nominal range:
Pin position
Default
No
Nominal range
(locked with Code 4 = No)
Turn
®
Code 4
Press
, Code 4 blinks
Turn
®
Pin position on lever (see relevant
section on attachment)
Press
Turn
®
Code 5
Press
, Code 5 blinks
Turn
®
Nominal travel/angle
Press
Select the initialization mode:
Initialization mode
Default
MAX
Turn
®
Code
6
Press
Turn
®
SUB
Press
to confirm
SUB
as the initialization
mode.
Enter the direction of action:
Direction of action
Default
ää
Turn
®
Code 7
Press
, Code 7 blinks
Turn
®
Direction of action (
ää
/
äæ
)
Press
Deactivate travel limit:
Travel limit
Default
100.0
Turn
®
Code 11
Press
, Code 11 blinks
Turn
®
No
Press
Change pressure limit and control parame-
ters:
Note:
Do not change the pressure limit
(
Code 16
). Only change the control param-
eters K
P
(
Code 17
) and T
V
(
Code 18
) if the
settings of the replaced positioner are
known.
66