Code
no.
Parameter
– Readings,
values [default setting]
Description
Note:
Codes with marked with an asterisk (*) must be enabled with
Code 3
prior to configuration.
6*
Initialization mode
(init
mode)
- continued -
MAN2: Manual setting 2 · For all globe valves with unknown
nominal range (OPEN and CLOSED position) · The
positioner determines travel/angle of rotation between
the manually selected OPEN (100 %) and the manually
selected CLOSED position (0 %)
SUB:
Substitute calibration · To replace a positioner while the
plant is running, with the least amount of disruption to
the plant
KP:
Fine tuning of the input filter · The valve moves through
its entire valve range.
NP:
Zero calibration · The zero point is recalibrated.
NOTICE
The valve moves briefly from the operating point
to the closed position!
7*
Direction of action
(w/x)
[
ää
] ·
äæ
· ESC
Direction of action of the set point in relation to the valve position
ää
:
Increasing/increasing: a globe valve opens as the set
point increases.
äæ
:
Increasing/decreasing: a globe valve closes as the set
point increases.
The direction of action is adapted to the change in closed direc-
tion as follows:
ATO: AIR TO OPEN · After initialization, the direction of ac-
tion remains increasing/increasing (
ää
), a globe valve
opens as the mA signal increases.
ATC:
AIR TO CLOSE · After initialization, the direction of ac-
tion changes to increasing/decreasing (
äæ
), a globe
valve opens as the mA signal increases.
8*
Lower travel/angle range
value
(lower x-range value)
[0.0] to 80.0 % of the nom-
inal range · ESC
Specified in mm or angle°,
provided
Code 4
is acti-
vated.
Lower range value for the travel/angle of rotation in the oper-
ating range.
Nominal range and characteristic are automatically adapted.
The operating range is the actual travel/angle of the valve and is
limited by the lower travel/angle range value (
Code 8
) and the
upper travel/angle range value (
Code 9
).
Usually, the operating range and the nominal range are iden-
tical. The nominal range can be limited to the operating range
by the lower and upper x-range values. Value is displayed or
must be entered.
See also the example in
Code 9
!
EB 8384-6 EN
85
Code list
Summary of Contents for 3730-6
Page 19: ...EB 8384 6 EN 19...
Page 51: ...EB 8384 6 EN 51...
Page 113: ...EB 8384 6 EN 113...
Page 114: ...114 EB 8384 6 EN...
Page 115: ...EB 8384 6 EN 115...
Page 116: ...116 EB 8384 6 EN...
Page 117: ...EB 8384 6 EN 117...
Page 118: ...118 EB 8384 6 EN...
Page 119: ...EB 8384 6 EN 119...
Page 120: ...120 EB 8384 6 EN...
Page 123: ...EB 8384 6 EN 123 diagnostic functions 11 Z Zero calibration 68 Index...