18
EB 8384-6 EN
Design and principle of operation
Options for Type 3730-6 Positioner
Binary input
· Galvanically isolated · Switching behavior configured over software
Active switching behavior (default setting)
Connection
For external switch (floating contact) or relay contacts
Electrical data
Open-circuit voltage when contact is open: max. 10 V, pulsed DC current with
peak value of 100 mA and RMS current 0.01mA when the contact is closed
Contact
Closed, R < 20
W
Switching state ON (default)
Open, R > 400
W
Switching state OFF (default)
Passive switching behavior
Connection
For externally applied DC voltage, reverse polarity protection
Electrical data
3 to 30 V · Destruction limit: 40 V · Current draw at 24 V: 3.7 mA
Voltage
> 6 V Switching state ON (default)
< 1 V Switching state OFF (default)
External position sensor
Travel
Same as positioner
Cable
10 m with M12x1 connector, designed for continuous flexing, flame retardant
acc. to VDE 0472, resistant to oils, lubricants, coolants as well as other corro-
sive media
Permissible ambient
temperature
–60 to +105 °C · Limits specified in the EC Type Examination Certificate addi-
tionally apply for explosion-protected devices.
Vibration immunity
Up to 10 g in the range between 10 and 2000 Hz
Degree of protection
IP 67
Summary of Contents for 3730-6
Page 19: ...EB 8384 6 EN 19...
Page 51: ...EB 8384 6 EN 51...
Page 113: ...EB 8384 6 EN 113...
Page 114: ...114 EB 8384 6 EN...
Page 115: ...EB 8384 6 EN 115...
Page 116: ...116 EB 8384 6 EN...
Page 117: ...EB 8384 6 EN 117...
Page 118: ...118 EB 8384 6 EN...
Page 119: ...EB 8384 6 EN 119...
Page 120: ...120 EB 8384 6 EN...
Page 123: ...EB 8384 6 EN 123 diagnostic functions 11 Z Zero calibration 68 Index...