Group E1: Output Terminals
Type
Function
code
Name
Setting range
Minimum
unit
Factory
default
Attribute
Multi-
function
digital
output
terminals
E1.00
Open collector output
OUT1
0: Converter is ready to run
1: Converter is running
2: DC brake active
3: Converter runs at zero speed
4. Frequency/speed arrival signal
5. Frequency level detection signal (FDT1)
6. Frequency level detection signal (FDT2)
7: Simple PLC phase completed
8: Under voltage / converter stop warning
9: Converter over load pre-warning
10: Motor over load pre-warning
11: Over torque
1
1
◆
E1.01
Open collector output
OUT2
1
1
◆
E1.02
Relay outputs
Pa, Pb and Pc
1
1
◆
E1.03
Frequency arrival
detection width
0.0 % − 20.0 %
(of maximum frequency b1.05)
0.1 %
5.0 %
◇
E1.04
Frequency detection
level FDT1
0.0 % − 100.0 %
(of maximum frequency b1.05)
0.1 %
90.0 %
◇
E1.05
Frequency detection
level FDT1 width
0.0 % − 100.0 %
(of maximum frequency b1.05)
0.1 %
5.0 %
◇
E1.06
Frequency detection
level FDT2
0.0 % − 100.0%
(of maximum frequency b1.05)
0.1 %
50.0 %
◇
E1.07
Frequency detection
level FDT2 width
0.0 % − 100.0 %
(of maximum frequency b1.05)
0.1 %
5.0 %
◇
E1.08
Converter over load
pre-warning level setting
20.0 % − 100.0 %
(of rated converter current)
0.1 %
100.0 % ◇
E1.09
Motor over load
pre-warning level setting
100.0 % − 250.0 %
(of rated motor current)
0.1 %
100.0 % ◇
Analog
output
terminals
E1.10
FM1 analog outputs
0: Output frequency / rotation speed
1: Set frequency / rotation speed
2: Output current
3: Torque current
4: Output voltage
1
0
◇
E1.11
FM1 channel mode
0:0 − 10 V or 0 − 20 mA
1:2 − 10 V or 4 − 20 mA
1
0
◇
E1.12
FM1 gain setting
0.00 − 10.00
0.01
1.00
◇
E1.13
FM2 analog outputs
0: Output frequency / rotation speed
1: Set frequency / rotation speed
2: Output current
3: Torque current
4: Output voltage
1
1
◇
E1.14
FM2 channel mode
0:0 − 10 V or 0 − 20 mA
1:2 − 10 V or 4 − 20 mA
1
0
◇
E1.15
FM2 gain setting
0.00 − 10.00
0.01
1.00
◇
DOK-RCON02-FV*********IB01-EN-P
Rexroth Frequency Converter Fv
Bosch Rexroth AG
77/219
Parameter Settings
Summary of Contents for Fv Series
Page 20: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 18 219...
Page 30: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 28 219...
Page 34: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 32 219...
Page 52: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 50 219...
Page 58: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 56 219...
Page 144: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 142 219...
Page 164: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 162 219...
Page 180: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 178 219...
Page 214: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 212 219...
Page 216: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 214 219...
Page 220: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 218 219...
Page 221: ...Notes DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv Bosch Rexroth AG 219 219...