Type
Function
code
Name
Setting range
Minimum
unit
Factory
default
Attribute
Start
or
stop
parame‐
ters
b1.16
Start mode
0: Start mode 1
1: Start mode 2
2: Rotation speed capture mode
1
0
◆
b1.17
Start frequency
0.00 − 15.00 Hz
0.01 Hz
0.50 Hz
◆
b1.18
Start frequency
hold time
0.0 − 10.0s
0.1s
0.0s
◆
b1.19
Stop mode
0: Decelerate to stop
1: Freewheel to stop
1
0
◆
DC
brake
b1.20
Startup DC brake time
0.0 − 20.0s (0.0 deactivates DC braking)
0.1s
0.0s
◆
b1.21
Shutdown DC brake
activation frequency
0.00 − 10.00 Hz
0.01 Hz
0.00 Hz
◆
b1.22
Shutdown DC brake time 0.0 − 20.0s (0.0 deactivates DC braking)
0.1s
0.0s
◆
b1.23
DC brake current
0.0 % − 150.0 % (of rated converter current) 0.1 %
0.0 %
◆
DOK-RCON02-FV*********IB01-EN-P
Rexroth Frequency Converter Fv
Bosch Rexroth AG
71/219
Parameter Settings
Summary of Contents for Fv Series
Page 20: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 18 219...
Page 30: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 28 219...
Page 34: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 32 219...
Page 52: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 50 219...
Page 58: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 56 219...
Page 144: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 142 219...
Page 164: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 162 219...
Page 180: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 178 219...
Page 214: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 212 219...
Page 216: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 214 219...
Page 220: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 218 219...
Page 221: ...Notes DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv Bosch Rexroth AG 219 219...