6.1.3
Operation Mode Description
Fig.6-3:
Operation mode description
6.1.4
Example of Operating Panel Operation
Fig.6-4:
Example of operating panel operation
6.2
Commission Process
6.2.1
Check and Preparation before Commissioning
1. Check if the wiring is correct. Particularly, ensure that the output termi‐
nals U, V and W of the converter are not connected to the power supply
and that the ground terminal is well grounded.
2. Ensure that there are no short circuits between terminals, live terminals
or short circuit to ground.
3. Ensure that terminal connections, connectors and screws are secure.
4. Ensure the motor is not connected to other loads.
5. Check that all inputs are off before powering on, to ensure that the con‐
verter will be started as expected and no unexpected action occurs.
6. Make the following checks after powering on:
●
Set frequency flashes on the display (without fault indication);
●
The displayed parameters match with the field application.
6.2.2
Notes on Commissioning
1. The converter has no internal contactor, and will be energized once the
main power supply is connected. When the Run key is pressed down (or
the control through terminals is selected), the converter will give output.
2. By factory default, the converter initially displays output frequency after
being energized. You may change it to another parameter as instructed
DOK-RCON02-FV*********IB01-EN-P
Rexroth Frequency Converter Fv
Bosch Rexroth AG
53/219
Commissioning
Summary of Contents for Fv Series
Page 20: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 18 219...
Page 30: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 28 219...
Page 34: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 32 219...
Page 52: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 50 219...
Page 58: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 56 219...
Page 144: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 142 219...
Page 164: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 162 219...
Page 180: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 178 219...
Page 214: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 212 219...
Page 216: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 214 219...
Page 220: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 218 219...
Page 221: ...Notes DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv Bosch Rexroth AG 219 219...