Group S1: Vector control
S1.00
Speed feedback proportional gain
Factory default 1.000
Setting range
0.000 − 10.000
Minimum unit
0.001
S1.01
Speed feedback integral time
Factory default 1.000s
Setting range
0.000 − 10.000s
(0.000 means inactive)
Minimum unit
0.001s
Used to adjust the speed dynamic response characteristics of vector control.
●
Larger proportional gain leads to faster response.
●
Too large proportional gain may cause oscillation.
●
Smaller proportional gain leads to slower response.
●
Larger integral time leads to slower dynamic response of the system
and the control on external disturbance is slowed.
●
Smaller integral time leads to faster dynamic response of the system.
●
Excessively small integral time may cause oscillation.
If the factory defaults can not meet the application requirements, the parame‐
ters can be adjusted in the following manner:
●
The proportional gain should be increased without causing oscillation.
●
The integral time should be decreased to allow the system to have quick
response and smaller overshoot.
Improperly set parameters may lead to excessive speed over‐
shoot or overvoltage faults during fall back from the overshoot.
S1.02
Torque limit
Factory default 150.0 %
Setting range
0.0 % − 200.0 %
(of rated motor torque)
Minimum unit
0.1 %
Used to to limit the maximum torque current of the converter during startup or
braking.
If a large brake torque is required, apply the torque limit funcion
together with brake.
S1.03
Slip compensation gain
Factory default 100.0 %
Setting range
0.0 % − 250.0 %
Minimum unit
0.1 %
Used to maintain constant motor speeds with load changes.
Increase this value when the motor is heavily loaded and has a
low speed, and vice versa.
S1.04
Torque control selection
Factory default 0
Setting range
0: Terminal control
1: Always active
Minimum unit
1
●
0: Terminal control
Bosch Rexroth AG
DOK-RCON02-FV*********IB01-EN-P
Rexroth Frequency Converter Fv
102/219
Parameter Settings
Summary of Contents for Fv Series
Page 20: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 18 219...
Page 30: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 28 219...
Page 34: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 32 219...
Page 52: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 50 219...
Page 58: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 56 219...
Page 144: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 142 219...
Page 164: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 162 219...
Page 180: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 178 219...
Page 214: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 212 219...
Page 216: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 214 219...
Page 220: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 218 219...
Page 221: ...Notes DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv Bosch Rexroth AG 219 219...