5.2.3
Control Circuit Wiring
●
Terminal GND is the common terminal for analog signals, and SC is the
common terminal for switch values. Do not ground these terminals.
Shielded or twisted-pair cables should be used for wiring terminals for
the control circuit and must be separated from the wiring of main circuit
and high current circuits (including the control circuit of 200 V relay).
●
Since the frequency control input signals are low power signals, two
contacts in parallel or a twin contact should be used for low power signal
current to avoid loose contact.
●
0.3 to 1.0 mm
2
cables are recommended for wiring of the control circuit.
●
Please strip the wire insulation for wiring of the control circuit, according
to the dimensions given below. Too long stripping may cause short cir‐
cuit of adjacent wires, and too short stripping may lead wires becoming
loose.
●
If a post terminal or single-conductor wire is used, use a cable with a di‐
ameter of less than 1.0 mm. If the cable is larger than 1.0 mm, the
screw may be stripped when being tightened up.
●
Tighten up screws with typically 0.8 Nm / 7 lb-in torque after the cables
are inserted into the terminals.
●
Cables may become disconnected and cause incorrect operation if not
tightened. However, over-tightening screws may break the component
to cause short circuit and incorrect operation.
5.2.4
Cable and Fuse Dimensions
The power cable dimensions and the fuse dimensions are based on the VDE
0298 (part 4) and the standard for the European countries EN 60204-1.
The dimension for flexible wiring is according to VDE 0298 (part 4) and for fix
wiring according to VDE 0298 (part 4) or IEC 60364-5 (operating temperature
at the conductor 90 ℃).
The cable and fuse dimensions for USA / Canada are based on UL 508A.
The manufacturer of the machine/installation is responsible for
conformity with regional provisions and other standards that are
relevant for the respective application and the place of installa‐
tion. Also factors, such as installation methods, grounding, insula‐
tion and over-voltage protection must be taken into consideration.
National standards, such as NFPA in the USA, regional provisions, ground,
operating temperature, operating cycles, over-voltage protection and system
configuration can have a decisive impact on the dimensioning of the cables
and therefore they must be given priority over the above factors.
If, as a consequence of this, further requirement and cable de‐
signs arise that are not mentioned in this documentation, contact
your Bosch Rexroth sales partner.
Recommendation on cable dimensioning:
1. Determines the power size of the frequency converter;
2. Determines country of use (e.g. “international without USA/Canada”);
3. Determines installation type (e.g. B1 or B2);
4. In table row “Nominal current fuse”, read corresponding fuse.
DOK-RCON02-FV*********IB01-EN-P
Rexroth Frequency Converter Fv
Bosch Rexroth AG
39/219
Installation
Summary of Contents for Fv Series
Page 20: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 18 219...
Page 30: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 28 219...
Page 34: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 32 219...
Page 52: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 50 219...
Page 58: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 56 219...
Page 144: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 142 219...
Page 164: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 162 219...
Page 180: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 178 219...
Page 214: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 212 219...
Page 216: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 214 219...
Page 220: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 218 219...
Page 221: ...Notes DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv Bosch Rexroth AG 219 219...