7.4.2
Category S: Standard Parameters
Group S0: V/F Control
Parameters of group S0 are only valid when 'Control mode' [b1.03] is ‘0: V/F
control’.
S0.00
V/F mode
Factory default 0
Setting range
0: Linear mode
1: Square mode
2: User-defined multipoint mode
Minimum unit
1
●
0: Linear mode
–
Suitable for constant torque load
(shown as 0 in
chapter "Group S0: V/F Control" on page 97
).
●
1: Square mode
–
Suitable for variable torque loads
(shown as 1 in
chapter "Group S0: V/F Control" on page 97
).
Fig.7-20:
Linear and square V/F curves
●
2: User-defined multipoint mode
–
Used to set a user defined V/F curve with parameters [S0.01] to
[S0.06]. Suitable for special applications (shown in
).
DOK-RCON02-FV*********IB01-EN-P
Rexroth Frequency Converter Fv
Bosch Rexroth AG
97/219
Parameter Settings
Summary of Contents for Fv Series
Page 20: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 18 219...
Page 30: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 28 219...
Page 34: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 32 219...
Page 52: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 50 219...
Page 58: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 56 219...
Page 144: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 142 219...
Page 164: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 162 219...
Page 180: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 178 219...
Page 214: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 212 219...
Page 216: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 214 219...
Page 220: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 218 219...
Page 221: ...Notes DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv Bosch Rexroth AG 219 219...