Between magnetic components (such as transformers, mains chokes
and DC bus chokes that are directly connected to the power connec‐
tions of the drive system) and the interference-free components and
lines between mains and filter including the mains filter in area A
If these distances are not kept, the magnetic leakage fields are injected to the
interference-free components and lines connected to the mains and the limit
values at the mains connection are exceeded in spite of the installed filter.
Cable Routing of the Interference-
free Lines to the Mains Connec‐
tion
Comply with a distance of at least 200 mm (distance d1 and d3 in the figure):
●
Between supply feeder or lines between filter and exit point from the
control cabinet in area A and the lines in area B and C
If this is impossible, there are two alternatives:
1.
Install lines in shielded form and connect the shield at several points (at
least at the begging and at the end of the line) to the mounting plate or
the control cabinet housing over a large surface area.
2.
Separate lines from the other interference-susceptible lines in areas B
and C by means of a grounded distance plate vertically attached to the
mounting plate.
Install the shortest possible lines within the control cabinet and install them
directly on the grounded metal surface of the mounting plate or of the control
cabinet housing.
Mains supply lines from areas B and C must not be connected to the mains
without a filter.
In case you do not observe the information on cable routing given
in this section, the effect of the mains filter is totally or partly neu‐
tralized. This will cause the noise level of the interference emis‐
sion to be higher within the range of 150 kHz to 40 kHz and the
limit values at the connection points of the machine or installation
will thereby be exceeded.
Routing and Connecting a Neutral
Conductor (N)
If a neutral conductor is used together with a three-phase connection, it must
not be installed unfiltered in zones B and C, in order to keep interference off
the mains.
Motor Blower at Mains Filter
Single-phase or three-phase supply lines of motor blowers, that are usually
routed in parallel with motor power cables or interference-susceptible lines,
must be filtered:
●
In drive system with only infeeding supply units, via the available three
phase filter of the drive system
When switching power off, make sure the blower is not switched off.
Loads at Mains Filter of Drive Sys‐
tem
●
Only operate allowed loads at the mains filter of the drive system!
Do not operate any motor blowers, power supply units, etc. at the mains
filter of the drive system.
Shielding Mains Supply Lines in
Control Cabinet
If there is a high degree of interference injection to the mains supply line with‐
in the control cabinet, although you have observed the above instructions (to
be found out by EMC measurement according to standard), proceed as fol‐
lows:
●
Only use shielded lines in area A
●
Connect shields to the mounting plate at the beginning and the end of
the line by means of clips
The same procedure may be required for long cables of more than 2 m be‐
tween the point of power supply connection of the control cabinet and the fil‐
ter within the control cabinet.
DOK-RCON02-FV*********IB01-EN-P
Rexroth Frequency Converter Fv
Bosch Rexroth AG
157/219
Technical Data
Summary of Contents for Fv Series
Page 20: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 18 219...
Page 30: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 28 219...
Page 34: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 32 219...
Page 52: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 50 219...
Page 58: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 56 219...
Page 144: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 142 219...
Page 164: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 162 219...
Page 180: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 178 219...
Page 214: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 212 219...
Page 216: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 214 219...
Page 220: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 218 219...
Page 221: ...Notes DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv Bosch Rexroth AG 219 219...