- 64 -
P0-14
Running
frequency lower
limit offset
Factory
default
0.00Hz
Set range
0.00Hz
~
upper frequency P0-12
When the frequency command is lower than the lower limit of P0-14, the inverter can be
stopped, run at the lower limit frequency or run at zero speed. What mode of operation can
be used through P8-14 (setting frequency lower than lower frequency operation mode) Set
up.
P0-17
acceleration time 1 Factory default
Motor type confirmation
Set range
0s
~
65000s
(
P0-19=0
)
P0-18
Deceleration 1
Factory
default
Motor type confirmation
Set range
0s
~
65000s
(
P0-19=0
)
The acceleration time refers to the time required for the frequency converter to
change from zero frequency to acceleration / deceleration reference frequency (P0-25),
see t1 in Figure 6-3. Deceleration time refers to the frequency converter from the
acceleration and deceleration reference frequency (P0-25 determined), deceleration to
zero frequency required time, see Figure 6-3
Figure6-3 acceleration/Deceleration time shows diagram
DSI-200 provides four groups of acceleration and deceleration time, the user can use the
digital input terminal S switch selection, four sets of acceleration and deceleration time
through the following function code settings:
Group one
:
P0-17
、
P0-18;
Group two
:
P8-03
、
P8-04;
Group three
:
P8-05
、
P8-06;