- 95 -
The output frequency is incremented or decremented by line.
1
:
S curve acceleration and deceleration A (static)
The output frequency is incremented or decremented according to the S curve. The S-
curve is used in places where gentle start or stop is required, such as elevators, conveyor
belts, etc.
2
:
S curve acceleration and deceleration B (dynamic)
Generally used for high-speed areas above the rated frequency of the need for rapid
acceleration and deceleration occasions.
P6-08
S Curve start time ratio Default value
30.0%
Set range
0.0%
~(
100.0%-P6-09
)
P6-09
S Curve start time ratio Default value
30.0%
Set range
0.0%
~(
100.0%-P6-08
)
Function codes P6-08 and P6-09 respectively define the start and end time ratios of the S
curve acceleration and deceleration A, and the two function codes are satisfied: P6 -08 +
P6-09 ≤ 100.0%.
P6-10
Stop way choose
Factory value
0
Set range
0
:
Decelerate to Stop 1
:
Coast to Stop
0
:
Decelerate to Stop
Once the stop command is input, the AC drive decreases the output frequency based on
the deceleration time to 0 and stop.
1
:
Coast to Stop
Once the stop command is input, the AC drive immediately stops output. The motor then
Coasts to stop based on the mechanical inertia.
P6-11
DC braking to stop start
frequency
Factory
default
0.00Hz
Setting
Range
0.00Hz
~
Max frequency
P6-12
DC braking to stop delay
time
Factory
default
0.0s
Setting
Range
0.0s
~
36.0s
P6-13
DC braking to stop current
Factory
default
50%
Setting
Range
0%
~
100%
P6-14
DC braking to stop time
Factory
default
0.0s