- 115 -
Figure 6-25 process PID schematic block diagram
PA-00
PID given source
selection
Factory default
0
Set range
0:PA-01 setting 1:AI1 2
:
AI2 3:AI3
4: high speed pulse input setting
(
S5
)
5:Communication given
6: multi-segment instructions
PA-01
PID given value
factory default
50.0%
Set range
0.0%
~
100.0%
This parameter is used to select the target volume of the process PID.
The set value of the process PID is the relative value, and the setting range is 0.0% ~
100.0%. The same PID feedback is the relative amount, the role of PID is to make the two
relative amount of the same.
PA-02
PID feedback source
selection
Factory default
0
Set range
0
:
AI1 1
:
AI2 2
:
AI3
3
:
AI1
-
AI2
4
:
high speed pulse input setting
(
S5
)
5
:
Communication given
6
:
AI1+AI2
7
:
MAX
(
|AI1|,|AI2|
)
8
:
MIN
(
|AI1|,|AI2|
)
This parameter is used to select the feedback channel of the process PID
。
The set value of the process PID is the relative value, and the setting range is 0.0% ~ 100.0%
PA-03
PID role direction
Factory default
0
Set range
0
:
Positive effect 1
:
reaction
Positive function: When the PID feedback signal is less than a given amount, the inverter
output frequency increases. Such as the tension of the tension control occasions.