- 31 -
P1-09
Mutual inductive
0.1mH
~
6553.5mH
Auto-tuning
dependent
★
P1-10
No-load current
0.01A
~
P1-03
Auto-tuning
dependent
★
P1-27
Encoder pulses
1
~
65535
1024
★
P1-30
A/B phase sequence of ABZ
incremental encoder
0: Forward
1: Reserve
0
★
P1-36
Encoder wire-break fault
detection
time
0.0: no operation
0.1s
~
10.0s
0.0s
★
P1-37
Motor auto-tuning method
selection
0: no operation
1: Asynchronous machine static
part of the parameters of self-
learning
2:asynchronous
machine
dynamic
complete
self-
learning
3:asynchronous machine static
complete self-learning
0
★
P2 Vector Control Parameters
P2-00
Speed loop proportional gain
1
1
~
100
30
☆
P2-01
Speed loop integral time 1
0.01s
~
10.00s
0.50s
☆
P2-02
Switch over frequency 1
0.00
~
P2-05
5.00Hz
☆
P2-03
Speed loop proportional gain
2
1
~
100
20
☆
P2-04
Speed loop integral time 2
0.01s
~
10.00s
1.00s
☆
P2-05
Switch over frequency 2
P2-02
~
max frequency(P0-10)
10.00Hz
☆
P2-06
SVC/FVC slip compensation
gain
50%
~
200%
100%
☆
P2-07
SVC Speed feedback filter
time
constant
0.000s
~
0.100s
0.015s
☆