- 38 -
P4-38 S1~S5 active mode selection 1
0: active high
1: active low
Bit: S1
Ten: S2
Hundred places: S3
Thousands of bits: S4
Million: S5
00000
★
P5 Output Terminals
P5-00
HDO terminal output mode
0: pulse output (HDP)
1: Switching output (HDY)
0
☆
Function
Code
Name
Set Range
default
Alteration
P5-01
HDY function selection
0: No output
1: The inverter is running
2: fault output (fault stop)
3: Frequency level detection
FDT1 output
4: frequency arrives
5: Zero speed operation (no
output at shutdown)
6: motor overload pre-alarm
7: Inverter overload pre-alarm
8: Set the count value to reach
9: Specifies that the count value
arrives
10: length to reach
11: PLC cycle is complete
12: The cumulative run time
arrives
13: Frequency limit
14: Torque limit
15: Ready to run
16: AI1> AI2
17: upper limit frequency
arrival
18: Lower frequency arrival
(operation related)
19: Under voltage status output
20: communication settings
21:Positioning completed
(reserved)
22: positioning close (reserved)
23: zero speed running 2 (also
output when stopped)
24: The total power-up time
arrives
25: Frequency level detection
FDT2 output
26: Frequency 1 reaches the
output
27: Frequency 2 reaches the
output
28: current 1 reaches the output
29: current 2 reaches the output
30: Timing arrival output
31: AI1 input is overrun
32: Under load
33: reverse running
0
☆
P5-02
function selection
(
RO1A-
RO1B-RO1C
)
2
☆
0
☆
1
☆
-
☆