- 108 -
Figure 6-22 Output current limit.
P8-38
Detection level of current 1
Factory
default
100.0%
Setting
Range
0.0%
~
300.0%
(
rated motor current
)
P8-39
Detection width of current 1
Factory
default
0.0%
Setting
Range
0.0%
~
300.0%
(
rated motor current
)
P8-40
Detection level of current 2
Factory
default
100.0%
Setting
Range
0.0%
~
300.0%
(
rated motor current
)
P8-41
Detection width of current 2
Factory
default
0.0%
Setting
Range
0.0%
~
300.0%
(
rated motor current
)
When the output current of the inverter reach into the positive and negative detection
width, the multi-function terminal HDO outputs the ON signal.
DSI-200 provides two sets of arrival current detection width parameters. Figure 6-23 is
functional schematic diagram.