current for 1 minutes, the alarm indicates motor overload fault; 150% * (P9-01) * motor
rated current for 60 minutes, then the alarm indicates motor overload.
The user needs to set the value of P9-01 correctly according to the actual overload capacity
of the motor. The parameter is too large to lead to overheating of the motor without
warning and become dangerous.
P9-02
Motor overload pre-
warning
coefficient
Factory default
80%
Setting Range
50%
~
100%
This function is used to give a pre-warning signal to the control system through the HDO
before the overload fault protection of the motor. The warning coefficient is used to
determine how warning is performed before the overload protection of the motor. The
greater the value, the smaller the amount of early warning.
When the output current of the inverter is larger than that of the overload reverse time
curve x P9-02, the multi-function terminal HDO of the inverter outputs "the motor
overload alarm" of ON signal.
P9-03
Over voltage stall
protection gain
Factory default
30
Setting Range
0
(
no over voltage stall)
)~
100
P9-04
Over voltage stall
protection voltage
Factory default
770V
Setting Range
650V~800V
The P9-03 function is equivalent to P3-24 and will change along with P3-24. The P9-04
function is equivalent to P3-22.
P9-09
Auto faulty reset times
Factory default
0
Setting Range
0
~
20
When the frequency inverter chooses to fault reset automatically, it is used to set the
number of automatic reset. If more than this value, the inverter remains in a state of faulty.
P9-10
Selection of HDO action during auto
Faulty reset
Factory default
1
Setting Range
0
:
Not act 1
:
act
If the inverter has set up the automatic reset function, the multi-function terminal HDO will
whether or not act during the automatic reset by P9-10 decide.
P9-11
Interval time of faulty
auto
reset
Factory default
1.0s
Setting Range
0.1s
~
100.0s
This parameter indicates the wait time between the self-alarm of the frequency converter
and the reset of the automatic fault.
P9-54
Frequency selection
for continuing to run
during fault reset
Factory default
0