- 113 -
Figure 6-24 action during instantaneous power failure
P9-63
Load lost protection
Factory default
0
Setting Range
0
:
invalid 1
:
valid
P9-64
Load lost detection level Factory default
10.0%
Setting Range
0.0%
~
100.0%
(
Rated motor current
)
P9-65
Load lost detection time Factory default
1.0s
Setting Range
0.0s
~
60.0s
If load lost protection function is valid, when output current of the inverter falls below
detection level (P9-64) for longer than time set in
F9-65, the inverter responds load lost protection to act automatically (protection action is
determined by P9-49, factory default is free stop). Once load recovers during protection,
the inverter recover to frequency reference.
P9-67
Over speed detection level Factory default
20.0%
Setting Range
0.0%
~
50.0%(max. frequency)
P9-68
Over speed detection time Factory default
1.0s
(
When is 10.0s,cancel muti-
speed detection
)
Setting Range
0.0s
~
60.0s
These function parameters define motor over speed detection that is effective only for