- 73 -
P3-03
Multipoint VF
frequency point P1
Factory
default
0.00Hz
Set range
0.00Hz
~
P3-05
P3-04
Multi point VF voltage
point V1
Factory
default
0.0%
Set range
0.0%
~
100.0%
P3-05
Multi point VF
frequency point P2
Factory
default
0.00Hz
Set range
P3-03
~
P3-07
P3-06
Multi point VF voltage
point V2
Factory
default
0.0%
Set range
0.0%
~
100.0%
P3-07
Multi point VF
frequency point F3
Factory
default
0.00Hz
Set range
P3-05
~
motor rated frequency
(
P1-04
)
Notes
:
No.2 motor rated frequency A2-04
P3-08
Multi point VF voltage
point V3
Factory
default
0.0%
Set range
0.0%
~
100.0%
P3-03 ~ P3-08 six parameters define multi-segment V / F curve.
Multi-point V / F curve according to the motor load characteristics to set, it should be
noted that the relationship between the three voltage points and frequency points must
meet: V1 <V2 <V3, F1 <F2 <F3. Figure 6-6 for the multi-point VF curve set diagram.
Low voltage setting at high frequencies may cause the motor to overheat or burn, and the
frequency converter may over-current stall or over current protection.
V1-V3
:
Multi-speed V / F Section 1-3 Voltage percentage
Vb
:
motor rated voltage
F1-F3
:
Multi-step speed V / F Division 1-3 Frequency percentage