- 63 -
Set range
0.00
~
max frequency
(
The frequency source selection
mode is valid for the digital setting
)
When the frequency source is selected as "digital setting", the function code value is the
frequency of the inverter.
P0-09
Motor rotation
direction
Factory default
0
Set range
0
:
same direction 1
:
opposite direction
By changing the function code, you can change the motor wiring without changing the motor
to achieve the purpose of changing the motor, its role is equivalent to adjust the motor (U, V,
W) any two lines to achieve the direction of rotation of the motor.
Note: After the parameter is initialized, the motor running direction will return to its original
state. For the system after debugging is strictly prohibited to change the motor steering
occasions with caution.
P0-10
Max output
frequency
Factory default
50.00 Hz
Set range
50.00Hz
~
500.00Hz
DSI-200 analog input, high-speed pulse input (S5), multi-segment instructions, as the
frequency of the respective 100.0% are relative to the P0-10 calibration.
P0-11
Running frequency
upper limit frequency
selection
Factory default
0
Set range
0
:
P0-12 settings 1
:
AI1 2
:
AI2
3
:
AI3 4:High speed pulse input
(
S5
)
5
:
Communication settings
Defines the source of the upper limit frequency. The upper limit frequency can be from the
digital setting (P0-12), or from the analog input, the high speed pulse input setting or the
communication reference.
When using the analog (AI1, AI2, AI3) setting, high-speed pulse input setting (S5) or
communication setting, similar to the main frequency source, see P0-03 introduction.
For example, when the torque control mode is adopted in the winding control field, the upper
limit frequency can be set by analog quantity in order to avoid the phenomenon of "speeding".
When the inverter is running to the upper limit frequency value, the inverter will run at the
upper limit frequency.
P0-13
Running
frequency upper
limit offset
Factory default
0.00Hz
Set range
0.00Hz
~
max frequency P0-10
When the upper limit frequency is set for analog or high speed pulse, P0-13 is used as the
offset of the set value, and the offset frequency is superimposed on the upper limit frequency
value of P0-11 setting as the final upper limit frequency setting value.