- 124 -
0: single run end stop
The inverter to complete a single cycle after the automatic shutdown, you need to
give a run command to start again.
1: the end of a single run to maintain the final value
After the inverter completes a single cycle, it automatically keeps the last running
frequency and direction.
2: has been circulating
After the inverter completes a cycle, the next cycle is automatically started until the
stop command is stopped.
PC-17
Simple PLC power loss
memory selection
Factory default
00
Set range
Bit
Power-down memory selection
0
:
Power-down no memory
1
:
Power-down memory
Ten
stop memory selection
0: no memory 1: downtime memory
PLC power-down memory is memory before power-down PLC running phase and
operating frequency, the next power from the memory stage to continue to run. Select no
memory, then each time the power is to restart the PLC process.
PLC shutdown memory is recorded when the previous record of the PLC running phase
and operating frequency, the next run from the memory stage to continue running. Select
no memory, then start each time to start the PLC process.
PC-18
Easy PLC run time 0
Factory default
0.0s
(
h
)
Set range
0.0s
(
h
)~
6553.5s
(
h
)
PC-19
Easy PLC paragraph 0
acceleration /
deceleration time
Factory default
0
Set range
0
~
3
PC-20
Simple PLC 1st run time Factory default
0.0s
(
h
)
Set range
0.0s
(
h
)~
6553.5s
(
h
)
PC-21
Easy PLC paragraph 1
acceleration /
deceleration time
Factory default
0
Set range
0
~
3
PC-22
Simple PLC 2nd run
time
Factory default
0.0s
(
h
)
Set range
0.0s
(
h
)~
6553.5s
(
h
)
PC-23
Easy PLC paragraph 2
acceleration /
deceleration time
Factory default
0