- 105 -
P8-25
Switch over frequency of
acceleration time 1 and
acceleration time 2
Factory default
0.00Hz
Setting Range
0.00Hz
~
max. frequency
P8-26
Switch over frequency of
deceleration
time 1 and deceleration time 2
Factory default
0.00Hz
Setting Range
0.00Hz
~
max. frequency
This function is valid when the motor is selected as motor 1 and is not switched over
through the S terminal to select the acceleration and deceleration time. During the
frequency inverter running process, not through the S terminal, but in accordance with the
frequency run range, choose different acceleration and deceleration.
Figure 6-19 Acceleration/Deceleration time switch over
During acceleration, if the running frequency is below P8-25, acceleration time 2 is
selected. If it is above P8-25, acceleration time 1 is selected.
During deceleration, if the running frequency is above P8-26, deceleration time 1 is
selected. If it is below P8-26, deceleration time 2 is selected.
P8-27
Set highest priority to
terminal JOG function
Factory default
0
Setting Range
0
:
invalid 1
:
valid
This parameter is used to set whether the terminal JOG function has the highest priority.
When the terminal JOG function is given priority, if the terminal JOG occurs during
running, the frequency inverter is switched to the terminal JOG status.